![A fully-controlled three-phase bridge converter is working from a 415 V, 50 Hz AC supply. It is supplying constant current of](https://www.gkseries.com/blog/wp-content/uploads/2023/08/A-fully-controlled-three-phase-bridge-converter-is-working-from-a-415-V-50-Hz-AC-supply.-It-is-supplying-constant-current-of-.jpg)
Q. A fully-controlled three-phase bridge converter is working from a 415 V, 50 Hz AC supply. It is supplying constant current of 100 A at 400 V to a DC load. Assume large inductive smoothing and neglect overlap. The rms value of the AC line current in amperes (round off to two decimal places) is
Solution:
Given that, output load current (I0) = 100 A
In a fully controlled three-phase bridge converter,
RMS value of the A.C. line current